Ironclad Automobile Parts Manuale Utente

Navigare online o scaricare Manuale Utente per Per l'auto Ironclad Automobile Parts. Ironclad Automobile Parts User Manual Manuale Utente

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
Vedere la pagina 0
INSTRUCTIONS FOR INSTALLATION,
OPERATION, AND MAINTENANCE OF
LEAD-ACID BATTERIES IN MOTIVE POWER
SERVICE
Section 28.00
I
nstructions for Installation,
Operation, and Maintenance of
Lead-Acid Batteries in
M
otive Power Service
TABLE OF CONTENTS
SECTION
SAFETY PRECAUTIONS 1
SPILLS AND RECYCLING 2
INTRODUCTION 3
FUNDAMENTALS OF A STORAGE BATTERY 4
CONSTRUCTION 5
INSPECTION OF BATTERY UPON RECEIPT
6
DRY CHARGED BATTERIES 7
INSTALLATION OF THE BATTERY 8
FAST CHARGING AND OPPORTUNITY CHARGING 9
OPERATION
10
TEMPERATURES 11
DISCHARGE CHARACTERISTICS 12
CHARGING EQUIPMENT 13
CHARGING CHARACTERISTICS 14
MAINTENANCE AND RECORDS 15
DETERMINATION OF CAPACITY 16
TROUBLESHOOTING 17
WATERING 18
CLEANING 19
ADJUSTING SPECIFIC GRAVITIES 20
STORAGE OF BATTERIES 21
ACCESSORIES
22
TOOLS 23
1. SAFETY PRECAUTIONS
a. Explosion can result from the gases produced by a
battery:
1. Do not smoke, use an open flame, or create arcs or
sparks in the vicinity of a battery
.
2. Only charge a battery in a well-ventilated area with
the cover of battery or compartment raised for maximum
ventilation.
3. Do not charge the battery at a current greater than
5 amps per 100 amp-hours capacity at the end of charge.
4. Every battery gives off hydrogen and oxygen during
recharge. Most of the gassing occurs after the 80%
point has been reached. As the breakdown of water
occurs oxygen and hydrogen are produced. The
concentration of the gasses is proportional to the current
being delivered to the battery.
To calculate the hydrogen produced use the following
formula, and ventilate the area as required. Hydrogen
must be ventilated in order to avoid an explosion.
Hydrogen concentrations of 4% or greater will cause an
explosion. When calculating assume all chargers in finish
rate at same time.
The National Fire Protection Association (NFPA) allows
up to 1% concentration. Make sure the ventilation system
can remove the hydrogen before it reaches
concentrations of 1% within the charging area.
Formula
0.00027 x (finish rate) x (number of cells) = cu. ft. of
hydrogen produced per min.
5. The ventilation system must also be designed to provide
removal of hydrogen and excess heat from the area directly
above charging batteries. Inlet air ducts should be placed
at shoulder height or lower so as to provide air movement
across the charging room and across batteries. Failure to
properly ventilate charging areas may result in employee
complaints of heat and “battery odor”.
b. Severe burns can be caused by the sulfuric acid contained
in the batteries covered by these instructions:
1. Do not get acid in eyes, on skin or clothing. In case of
contact, flush immediately and thoroughly with clean
water for at least 15 minutes. Obtain medical attention when
eyes are affected.
2. In handling sulfuric acid, wear a face shield, plastic or
rubber apron, and gloves.
A
void spilling acid.
3. PRO W
AS
H
TM
neutralizing and cleaning solution or
bicarbonate of soda solution (one pound to a gallon
water) will neutralize any acid accidentally spilled. Apply
the PRO W
ash solution until it turns yellow (bicarbonate
of soda solution stops bubbling), then rinse with clear
water. Do not allow any of this solution to enter the cells.
When diluting concentrated acid, always add acid to
water, never vice versa. Pour slowly and stir constantly,
to avoid excessive heat or violent chemical reaction.
4. Batteries and sulfuric acid should be handled only by
persons who have been instructed on the potential
chemical hazards, in accordance with the OSHA
29 C.F
.R.
1910.1200, Hazard Communication Standard. Refer to
EnerSys Material Safety Data Sheet (MSDS) for
lead-acid batteries.
c. The battery is electrically live at all times:
1. Keep the top of the battery clean and dry to prevent
ground shorts and corrosion.
2. Do not lay metallic objects on the battery; insulate all
tools used in working on the battery to prevent short circuits.
Also remove all jewelry before working on the battery
.
TUBULAR SINCE 1910
TM
Vedere la pagina 0
1 2 3 4 5 6 ... 10 11

Sommario

Pagina 1 - OPERATION, AND MAINTENANCE OF

INSTRUCTIONS FOR INSTALLATION,OPERATION, AND MAINTENANCE OFLEAD-ACID BATTERIES IN MOTIVE POWERSERVICESection 28.00Instructions for Installation,Operat

Pagina 2 - 4. FUNDAMENTALS

SERVICE TOOLS0*1. CELL LIFTER - Belt type cat. #SS-5746*02. CROSS LINK PUDDLING DAM - cat. #SS-5749*03. CABLE LUG PUDDLING DAM - cat. #SS-57470*4. CON

Pagina 3 - BATTERIES

™Section 28.00 Rev. H 11/06 © 2006 EnerSys All Rights Reserved.Trademarks are the property of EnerSys and its affiliates unless otherwise noted.G

Pagina 4 - CHARGING PROCEDURES

3. Be especially careful when working on batteryterminal connections. Do not connect any two or moreterminals together unless the connection is a prop

Pagina 5 - 13. CHARGING EQUIPMENT

what you know about a battery’s volts, amps, and ampere-hours,you’re ready to easily change those numbers into the final keyconcept, watts.Watt,W.: Us

Pagina 6 - 15. MAINTENANCE AND

4. Give the battery an equalizing charge but keep resettingthe charger to the equalize position until the specific gravitiesremain constant for a per

Pagina 7 - 17. TROUBLESHOOTING

In sub-freezing temperatures, water should be added justbefore charging is completed to insure prompt mixingwith the electrolyte. Otherwise it may fre

Pagina 8 - VENT WELL

14. CHARGINGCHARACTERISTICSa. Only EnerSys approved charging methods should beused. To maximize life, charging should not result inexcessive gassing

Pagina 9 - OTHER OPTIONAL ACCESSORIES:

16. DETERMINATION OFCAPACITYa. A battery's capacity will, of course, decrease toward theend of its life. Assuming no specific cause of trouble,

Pagina 10

e. Another convenient way to ensure proper fill levels is theuse of a single point watering (SPW) system. The EnerSysBattery Irrigation System or EZ

Pagina 11

i. EnerSys Pro-Meter #94870. This shirt pocket sizedmeter is versatile for 13 ranges in AC, DC and OHM readings.It has an audible continuity signal an

Commenti su questo manuale

Nessun commento